Permit: T03CM01582

Parcel: 13613001P

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
06/17/2003 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*/REPAIR LEAKS IN GREASE DUCT WELDS.
06/16/2003 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY
06/13/2003 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PROVIDE CONDENSATE DRAIN LINES AS PER PLANS 2) FIRE WRAP NOT INSTALLED PER MANUFACTURERS SYSTEM. "FIRE TEMP WRAP" IS A TWO LAYER SYSTEM. FOLLOW THE INSTALLATION INSTRUCTIONS. DO NOT TAPE SEAMS AND JOINTS, WE NEED TO BE ABLE TO CONFIRM PROPER OVERLAPS. ALL CUT EDGES REQUIRE TAPE. NEED TO SEE GREASE DUCT AND WELDS PRIOR TO FIRE WRAP. LEAVE INSTALLATION INSTRUCTIONS ON SITE 3) STRAP ALL DUCT UP OFF OF LIGHTS AND GRID. INSULATE ALL BARE METAL ON A/C DUCTS. RECALL FOR INSPECTION. NOTE: BE SURE FIRE WRAP EXTENDS ALL THE WAY TO TOP OF GREASE DUCT