Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/REPAIR LEAKS IN GREASE DUCT WELDS. |
| 06/16/2003 |
MECHANICAL - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOT READY |
| 06/13/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE CONDENSATE DRAIN LINES AS PER PLANS 2) FIRE WRAP NOT INSTALLED PER MANUFACTURERS SYSTEM. "FIRE TEMP WRAP" IS A TWO LAYER SYSTEM. FOLLOW THE INSTALLATION INSTRUCTIONS. DO NOT TAPE SEAMS AND JOINTS, WE NEED TO BE ABLE TO CONFIRM PROPER OVERLAPS. ALL CUT EDGES REQUIRE TAPE. NEED TO SEE GREASE DUCT AND WELDS PRIOR TO FIRE WRAP. LEAVE INSTALLATION INSTRUCTIONS ON SITE 3) STRAP ALL DUCT UP OFF OF LIGHTS AND GRID. INSULATE ALL BARE METAL ON A/C DUCTS. RECALL FOR INSPECTION. NOTE: BE SURE FIRE WRAP EXTENDS ALL THE WAY TO TOP OF GREASE DUCT |