Permit: T03CM01582

Parcel: 13613001P

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/14/2003 PLUMBING - ROUGH, SOIL Approved
05/08/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*
1.) MUST PROVIDE WATER TEST ON
SYSTEM AS REQUIRED
2.) DO NOT COVER.
05/06/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*REMOVE CO & INSTALL APPROVED FITTING PROVIDE APPROVED REVISED PLAN BY NEXT INSP.
05/02/2003 PLUMBING - ROUGH, SOIL Denied 1.) ROUGH PLBG. IS NOT TO APPROVAL PLAN
2.) CAN NOT HAVE A FLAT FACED BUSHING IN A HORIZONTAL POSITION. SEE SECTION: 311.5 94 UPC INTERPETATIONS.
3.) WILL REQUIRE A REVISED & APPROVED PLAN ON WASTE & VENT SYSTEM AND P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG. DRAIN.
4.) NOTE: CHECK WITH HEALTH DEPTH ON GREASE TRAP LOCATION ABOVE FLOOR.