Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR C OF O. |
| 11/13/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ DUCT SMOKE DETECTOR NOT WORKING ROOM 3. RECALL FOR INSPECTION. |
| 10/15/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ CORRECTIONS HAVE NOT BEEN MADE. OK FOR TEMP C OF O. |
| 10/14/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ ISOLATE REFER LINES WHERE THEY CONNECT TO FAN COIL TO PREVENT ABRASION ON CABINET OF FAN COIL. NEED TO SEE ALL DUCT SMOKE DETECTORS POWERED UP. CONDENSORS ON ROOF ARE OK. |