Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK 2) OK TO COVER WALLS | |
| 05/06/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) CLOSET FLANGES NOT SECURED 2.) NO WATER TEST ON ABS 3.) N/H BAND NOT APPROVED CONNECTOR BETWEEN ABS AND N/H. 4.) A TRAP ARM MAY ONLY CHANGE DIRECTION 90 5.) OVER NOTCHED STUD ON FLOOR JOIST. 6.) PLUMBERS TAPE NOT APPROVED STRAP. 7.) HAVE PLUMBER CHECK ALL WORK BEFORE CALLING INSPECTION. 8.) ALL HORIZONTAL PIPING TO BE SUPPORTED |