Permit: T03CM01561

Parcel: 11504549A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM01561

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK 2) OK TO COVER WALLS
05/06/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) CLOSET FLANGES NOT SECURED
2.) NO WATER TEST ON ABS
3.) N/H BAND NOT APPROVED CONNECTOR BETWEEN ABS AND N/H.
4.) A TRAP ARM MAY ONLY CHANGE DIRECTION 90
5.) OVER NOTCHED STUD ON FLOOR JOIST.
6.) PLUMBERS TAPE NOT APPROVED STRAP.
7.) HAVE PLUMBER CHECK ALL WORK BEFORE CALLING INSPECTION.
8.) ALL HORIZONTAL PIPING TO BE SUPPORTED