Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T03CM01560
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2003 | PLUMBING - PROGRESS | Approved | 1.) CORRECTION MADE OK 2.) WILL LOOK AT CRIPPLE WHERE STUD OVER NOTCHED WHEN I REINSPECT #227. 3.) OK TO COVER AFTER I WITNESS JOIST REPAIR. |
|
05/06/2003 | PLUMBING - PROGRESS | Denied | IVRS - Inspection 0999* 1.) NO WATER TEST ON ABS. 2.) CLOSET FLANGES NOT SECURED 3.) PLUMBERS TAPE NOT APPROVED STRAP. 4.) N/H BAND NOT APPROVED FOR ABS. 5.) A SANTEE MAY NOT LONG LAY ON ITS BACK. 6.) A VENT MUST RISE AT LEAST 6" ABOVE OVER FLOW BEFORE. 7.) OVER NOTCHED FLOOR JOIST INSTALL FLOOR DRAINS (SHOWER) 8.) THIS MAY NOT BE A COMPLETE LIST, HAVE PLUMBER CHECK ALL WORK BEFORE CALLING INSPECTION. |