Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T03CM01556
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/27/2004 | FIRE SPKLR - FINAL | Approved | OK FOR C OF O | |
02/24/2004 | FIRE SPKLR - FINAL | Partial Approval | Partial approval for Temporary C of O to allow furnishings in the building. Preaction system must be acceptance tested prior to occupancy of protected room. | |
02/18/2004 | FIRE SPKLR - FINAL | Denied | 1. Three sprinklers located in excess of 7'-6" from walls. 2. Preaction sprinkler system must be acceptance tested prior to occupancy of protected room. 3. Install fire sprinkler under overhead door. 4. Relocate fire sprinkler in Front Office Hallway. 5. Provide spare sprinkler box at riser. |