Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM01556
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/11/2004 | ELECTRIC - INTERMEDIATE | Denied | ARTICLES 400, 410, 604, & 605, PROHIBIT THE WIRING METHOD BEING USED ON THE FURNITURE PARTITIONS. WIRING OF THE PARTITIONS MUST BE DONE IN ACCORDANCE WITH THE MANUFACTURERD INSTRUCTIONS. PLEASE FURNISH THIS INSPECTOR A COMPLETE SET OF THE MANUFACTURERS INSTRUCTIONS. | |
02/17/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/05/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ALL SUSPENDED CEILINGS , OFFICES AND CONFERENCE ROOMS | |
01/28/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
12/15/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
12/04/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ FAN COIL 1-A REMOVE OBSTACLES FROM ELECTRIC CONTROL BOX. BATHROOM WALLS ROUGH IN OK. | |
12/02/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) GROUND RING FOR ANTENNA TOWER. 2) INSTALLATION OF FLOUR FIXTURES IN HIGH BAYS. | |
11/27/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
11/19/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ HI-BAY AREA. | |
11/17/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OFFICES - WEST CENTER. | |
11/12/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OFFICES- CENTER | |
11/07/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OFFICE CUBICLES EAST OF HALL ON EAST END 2) OFFICES NORTH WALL-NORTH OF HALL | |
11/04/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ PERIMETER WALLS - OFFICE SECTION. |