Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T03CM01512

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2003 PLUMBING - ABOVE CEILING Approved IVRS - Inspection 0000*
06/24/2003 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) PLEASE CORRECT YOUR SUITE NUMBER ON PERMIT, IT IS NOT SUITE #190 CHANGE TO #130 BY NEXT INSPECTION 2) ICE MAKER DRAIN AND ICE BIN DRAIN MAY NOT BE COMBINED. REMEMBER GREATER THAN FIVE FEET REQUIRED TO BE DIRECTLY TRAPPED 3) BELLS AND WHISTLES ON MIXING VALVE MISSING ALSO ? PUMP 4) NO UNIONS ON GAS PIPING 5) ALL HOT WATER PIPING TO BE INSULATED 6) REVISED APPROVED PLAN ON SITE
05/12/2003 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection 0000*