Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2003 |
PLUMBING - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 06/24/2003 |
PLUMBING - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE CORRECT YOUR SUITE NUMBER ON PERMIT, IT IS NOT SUITE #190 CHANGE TO #130 BY NEXT INSPECTION 2) ICE MAKER DRAIN AND ICE BIN DRAIN MAY NOT BE COMBINED. REMEMBER GREATER THAN FIVE FEET REQUIRED TO BE DIRECTLY TRAPPED 3) BELLS AND WHISTLES ON MIXING VALVE MISSING ALSO ? PUMP 4) NO UNIONS ON GAS PIPING 5) ALL HOT WATER PIPING TO BE INSULATED 6) REVISED APPROVED PLAN ON SITE |
| 05/12/2003 |
PLUMBING - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |