Permit: T03CM01509

Parcel: 10408077C

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
11/21/2003 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection 0000*/ 1) REVIEWED WATER PIPING INSTALLATION AT METER. 2) ROOF DRAINS OK. OK TO COVER ALL AREAS.
09/09/2003 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*
09/07/2003 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*/ 1) 3" PVC SCHEDULE 40 FROM RPPBP TO EDGE OF BLDG OK TO COVER 2) REPLACE PVC WITH COPPER UNDER BLDG 3) WATER METER AND CONNECTIVE PIPING NOT INSTALLED PER PLAN. PLAN CALLS FOR 2-1 1/2" METERS. ONE 2" METER INSTALLED. ALSO PER MARK TITUS WITH TUCSON WATER. METERS AND RPPBP TO BE THE SAME SIZE THEN CONNECTED TOGETHER DOWNSTREAM. PLEASE CLARIFY AND REVISE PLAN ACCORDINGLY