Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 11/21/2003 |
PLUMBING - YARD WTR LINE/TEST |
|
Approved |
IVRS - Inspection 0000*/ 1) REVIEWED WATER PIPING INSTALLATION AT METER. 2) ROOF DRAINS OK. OK TO COVER ALL AREAS. |
| 09/09/2003 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection 0000* |
| 09/07/2003 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) 3" PVC SCHEDULE 40 FROM RPPBP TO EDGE OF BLDG OK TO COVER 2) REPLACE PVC WITH COPPER UNDER BLDG 3) WATER METER AND CONNECTIVE PIPING NOT INSTALLED PER PLAN. PLAN CALLS FOR 2-1 1/2" METERS. ONE 2" METER INSTALLED. ALSO PER MARK TITUS WITH TUCSON WATER. METERS AND RPPBP TO BE THE SAME SIZE THEN CONNECTED TOGETHER DOWNSTREAM. PLEASE CLARIFY AND REVISE PLAN ACCORDINGLY |