Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/10/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 09/29/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ABS DWV THRU ROOF OK. WATER TEST OK. CLOSET FLANGES OK. 2) COPPER OK. PRESSURE TEST OK. 3) A CONDENSATE DRAIN MAY NOT CONNECT TO A SINK DRAIN (TAILPIECE) 4) GAS OK. |
| 09/28/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 09/15/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/1) SEWER HCS FROM INTERCEPTOR TO BLDG DRAIN TO CONNECTION AT HCS/MAIN OK. WATER TEST OK. OK TO COVER. 2) OVERHEAD GAS PIPING OK EXCEPT FOR WATER HEATER DROP. 60# TEST OK. |
| 07/22/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ INLET AND OUTLET INCLUDING VENT OK TO INTERCEPTOR. OK TO COVER. |
| 06/30/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) 3" TYPE "K" WATER SERVICE UNDER SLAB OK, SILFOS'D JOINT-OK, WRAPPED PIPE-OK 2) OK TO COVER |