Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01496
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ OK FINAL | |
| 06/25/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) WE HAVE EXCESSIVE PAINT ON TERMINALS AND LOOSE CONNECTIONS. 2) TIGHTEN LOOSE FLEX AND M/C FITTINGS AND CONDUIT. 3) FILLER BLANK IS NEEDED FOR PANEL. 4) BOND ROOF JUNCTION BOX 250-148. 5) SUPPORT CONDUIT WITHIN 3' OF BOXES. RECEIVED LETTER AUTHORIZING USE OF ROMEX WIRE. | |
| 04/21/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) PLEASE PROVIDE LETTER AUTHORIZING USE OF NM CABLE. 2) FINISH BOOKCASE WALL IN SEATING ROOM. |