Permit: T03CM01491

Parcel: 11804165A


Addresses:

1639 W SAN LUIS BL


Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T03CM01491

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2003 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
12/05/2003 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) REVISE LINTELS FOR APPROVAL BY CITY OF TUCSON (ALL ARE 1/4") 2) FIREPLACE DOES NOT MEET CODE FOR REINFORCEMENT
12/02/2003 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) PROVIDE ACCESS TO INSPECT ALL WALLS 2) FIRE PLACE HAS BEEN BUILT WITHOUT INSPECTION 3) LINTELS DO NOT MATCH DETAILS
11/05/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1ST LIFT./ NOTE: 8X8X16 UTILIZED WITH REINFORCEMENT AT 48" O.C. ( PLAN SHOWS SLUMP BLOCK WITH REINFORCMENT AT 32" O.C.)
10/10/2003 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection 0000*
10/08/2003 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection 0000*
08/05/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*