Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 06/20/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ALL WIRING IN PATIENT CARE FOR EQUIPMENT TO BE AS PER ARTICLE 517 2) SUPPORT M/C CABLE WITHIN 12" OF BOXES 3) PREVENT ELECTRIC CONTACT WITH PLUMBING COPPER LINES 4) WALLS OK |