Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/13/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 05/05/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) 2 FULL LENGTH 2 X 4'S REQUIRED AT HOLDOWN 2) COMPLY WITH DETAIL 7 SHEET 2 HOLDOWN REQUIRED AT 4 X 4 POST AT GARAGE 3) PENETRATION FOR RED HEADS AT FRONT PORCH COL. SUB-STANDARD. WHAT SIZE, LENGTH, BOLTS WERE USED?-VALUE FOR BOLTS THIS CLOSE TO EDGE OF STEM A PROBLEM WITH UPLIFT VALUE CHECK WITH ENGINEER OF RECORD FOR REPAIR |