Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/14/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 06/03/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/22/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NAILS NOT ALLOWED THRU ELECTRIC BOXES TO SUPPORT BOXES. REMOVE NAILS AND SUPPORT WITH SCREWS ON ONE SIDE OR CHANGE BOXES TO REPAIR BOXES 2) METAL ELECTRIC BOXES REQUIRE PLASTIC BUSHINGS IN ALL KNOCK OUTS 3) ALL METAL ELECTRIC BOXES MUST BE GROUNDED 4) UNTREATED WOOD CANNOT BE IN CONTACT WITH CONCRETE OR LOCATED WITHIN 6" OF SOIL 5) OPEN A SECTION OF NORTH AND EAST WALL ALONG BOTTOM FOR A LENGTH OF 24" AND 12" HIGH 6) WINDOW IS TO SMALL FOR EMERGENCY EXIT. OPENING MUST BE A MINIMUM OF 20" WIDE AND 24" HIGH WITH MINIMUM SIZE OF OPENING 5.7 SQUARE FEET MAXIMUM SILL HEIGHT 44" 7) NON OPENING BARS ARE NOT ALLOWED ON BEDROOM WINDOWS 8) HARD WIRED SMOKE DETECTORS REQUIRED IN NEW BEDROOM |