Permit: T03CM01441

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/21/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/1) CORRECTIONS MADE OK. 2)PLUMBING FINAL OK. 3) OK FOR C OF O PENDING ANY OTHER INSPECTION AND VERIFICATION OF CERTIFICATION OF 3/4" RPZ. WATTS 009 # 139570