Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM01441
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2003 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*/ 1) APPROVED REVISED PLAN ON SITE. 2) N/H UNDERGROUND INSTALLED PER PLAN. 3) OK TO BACKFILL. | |
07/08/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 3005- PLUMBING ROUGH/SOIL. 1) NO APPROVED PLAN ON SITE. 2) NEED REVISED APPROVAL PLAN, IT MUST REFLECT INSTALLATION, ON SITE FOR INSPECTION. | |
07/06/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1) THIS IS A COMMERCIAL INSTALLATION WHERE IS YOUR WASTE AND VENT ISOMETRIC DRAWING? 2) WATER TEST FOR N/H UNDERGROUND OK. WATER TEST ONE RISER TO TEN FEET OK. 3) NON GREASE PRODUCING FIXTURES MAY NOT DISCHARGE.THRU GREASE TRAP IE: CONDENSATE WASTE THRU FLOOR SINGL 4) EACH FIXTURE CONNECTED TO A GREASE TRAP TO HAVE A LISTED FLOW CONTROL DEVICE INSTALLED IN A READILY ACCESSIBLE AREA INSTALLED IN THE TAILPIECE R ON THE OUTLET SIDE OF THE TRAP. 5) CONTRACTOR OK TO BACKFILL UNDERGROUND N/H SUBJECT TO APPROVED PLAN. 6) MISSING PART OF PLUMBING PLAN, HAVE APPROVED PLAN ON SITE. |