Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/22/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 12/19/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) VENT 90 DEGREE FITTING NOT ALLOWED TO BE INSTALLED IN SHOWER DRAIN-MUST USE A LONG SWEEP 90 DEGREE BEND FITTING. REPLACE FITTING AND RETEST 2) I COULD NOT LOCATE YOUR PLAN/PERMIT. THEY MUST BE ON SITE FOR INSPECTION |
| 12/10/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE TEST 10' HIGH (WATER) 2) CAP ALL VENTS AND DRAINS EXCEPT FOR ONE-EXTEND 10' 2) AB'S SOIL PLUMBING MUST BE UNDER PRESSURE WHEN INSPECTOR IS ON SITE 3) UNCOVER ALL JOINTS |
| 12/08/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) IMPROPER VENTING AT WATER CLOSET |