Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM01429

Parcel: 10714139F


Addresses:

81 W JACINTO ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/07/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
07/30/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) WALL ROUGH-IN OK
07/28/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*/ 1) DO NOT BUNDLE CABLES. UNDO BUNDLES - ADD 2X4 BACKING - AND STAPLE OFF SEPARATELY. 2) DO NOT USE "TY-RAP" NYLON TIES. THESE ARE NOT APPROVED MC FASTENERS. 3) ADD BOND BUSHING TO NIPPLE FROM MAIN DISCONNECT TO SLAB PANEL. 4) ADD GROUND BAR TO PANEL. NUETRAL AND GROUND MUST BE SEPARATED. 5) FLOOR PLAN REVISION REQUIRED FOR BATHROOM. 6) FLOOR PLAN REVISION REQUIRED FOR MAIN FLOOR. 7) SWITCH BOX MISSING AT REAR. 8) A/C WIRING? 9) CHANGES IN EXTERIOR LIGHTING?