Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/07/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/30/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WALL ROUGH-IN OK |
| 07/28/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*/ 1) DO NOT BUNDLE CABLES. UNDO BUNDLES - ADD 2X4 BACKING - AND STAPLE OFF SEPARATELY. 2) DO NOT USE "TY-RAP" NYLON TIES. THESE ARE NOT APPROVED MC FASTENERS. 3) ADD BOND BUSHING TO NIPPLE FROM MAIN DISCONNECT TO SLAB PANEL. 4) ADD GROUND BAR TO PANEL. NUETRAL AND GROUND MUST BE SEPARATED. 5) FLOOR PLAN REVISION REQUIRED FOR BATHROOM. 6) FLOOR PLAN REVISION REQUIRED FOR MAIN FLOOR. 7) SWITCH BOX MISSING AT REAR. 8) A/C WIRING? 9) CHANGES IN EXTERIOR LIGHTING? |