Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2003 |
ELECTRIC - UFER |
|
Approved |
IVRS - Inspection 0000* CORRECTIONS REQUIRED 1) BOTH ENDS SIDES OF THE OFFSET NIPPLE BETWEEN METER CAN AND MAIN SWITCH MUST BE BONDEC. ADD BOND BUSHING 2) THE UFER WIRE MUST BE MOVED TO THE LUG BELOW THE NEUTRAL AT MAIN DISCONNECT. STACKING TERM LUGS IS PROHIBITED. |