Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2005 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* OK FOR FINAL |
| 01/26/2005 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* PARTIAL. PROVIDE SCREENS IN COMBUSTION AIR VENTS ON ROOF. SECURE ELEC. DISCONNECTS. PROVIDE CLEARANCE FROM REFER LINES TOUCHING FURNACE VENTS. CAP OFF SECONDARY DRAIN OUTLETS ON COILS. |