Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2005 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection :* |
| 04/09/2004 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLANS CALL FOR #2-4 SERVICE. SERVICE CANNOT BE RUN IN RACEWAY SYSTEM. ALSO 1 1/4" PVC IS NOT BIG ENOUGH FOR #2 CONDUCTORS AND GROUND. YOU WILL NEED 3-2" AND 1-#6 WHICH WILL BE CONDUCTOR OVER FILL FOR CONDUIT |
| 04/02/2004 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ OK 6 - 1ΒΌ" PVC CONDUITS SUBJECT TO PLANS. NO PLANS ON SITE. |
| 02/11/2004 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ UFER - 2 UNITS. |
| 02/10/2004 |
ELECTRIC - UNDERGROUND |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLANS CALL FOR 1/0 TO REBAR, HAVE #4 |