Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
02/11/2005 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
04/09/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) PLANS CALL FOR #2-4 SERVICE. SERVICE CANNOT BE RUN IN RACEWAY SYSTEM. ALSO 1 1/4" PVC IS NOT BIG ENOUGH FOR #2 CONDUCTORS AND GROUND. YOU WILL NEED 3-2" AND 1-#6 WHICH WILL BE CONDUCTOR OVER FILL FOR CONDUIT
04/02/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ OK 6 - 1ΒΌ" PVC CONDUITS SUBJECT TO PLANS. NO PLANS ON SITE.
02/11/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ UFER - 2 UNITS.
02/10/2004 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*/ 1) PLANS CALL FOR 1/0 TO REBAR, HAVE #4