Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T03CM01418
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2004 | PLUMBING - PROGRESS | Approved | ||
01/03/2004 | PLUMBING - PROGRESS | Partial Approval | ||
11/10/2003 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000*/ 15TH FLOOR REVISED PLAN ADDRESS VENTS AND WATER HEATER LOCATION - OK TO COVER THESE AREAS. | |