Permit: T03CM01365

Parcel: 132150040


Addresses:

750 E EVANS BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/23/2004 ELECTRIC - FINAL Approved IVRS - Inspection :* OK FOR C OF O
08/31/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/15/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ OK FOR TEMP C OF O. CALL FOR FINAL AFTER 3RD COMPRESSOR INSTALLED.
06/10/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) NEED TO VERIFY PANEL P-3 SUITABLE FOR USE AS SERVICE EQUIP. PER PLAN. 2) SEAL PENETRATIONS THRU COOLER WALL TO PREVENT CONDENSATION BUILD UP IN PANEL. 3) INSTALL 3RD COMPRESSOR FOR AC. 4) INSTALL LISTED BOLT DOWN HARDWARE FOR MAIN BACK FED 50 AMP BREAKER IN PANEL P-2. 5) LABEL PANEL P-3.