Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* OK FOR C OF O |
| 08/31/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 06/15/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ OK FOR TEMP C OF O. CALL FOR FINAL AFTER 3RD COMPRESSOR INSTALLED. |
| 06/10/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) NEED TO VERIFY PANEL P-3 SUITABLE FOR USE AS SERVICE EQUIP. PER PLAN. 2) SEAL PENETRATIONS THRU COOLER WALL TO PREVENT CONDENSATION BUILD UP IN PANEL. 3) INSTALL 3RD COMPRESSOR FOR AC. 4) INSTALL LISTED BOLT DOWN HARDWARE FOR MAIN BACK FED 50 AMP BREAKER IN PANEL P-2. 5) LABEL PANEL P-3. |