Permit: T03CM01340

Parcel: 13308004G

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM01340

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/02/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINALS.
05/01/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE COMPLETE ITEMS #4 & 5 OF PREVIOUS INSPECTION.
04/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) an extender ring will be needed in cup board to protect combustable use an approved ring. metal is not approved.
2.) maintain working clearence infront of subpanel.
3.) correctly identify ungrounded conductors at both ends.
4.) breaker to be sized per ampacity of conductors 336-26.
5.) new switches to be grounded 380-9.
6.) tighten water heater flex connectors.