Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINALS. | |
| 05/01/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*PLEASE COMPLETE ITEMS #4 & 5 OF PREVIOUS INSPECTION. | |
| 04/17/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) an extender ring will be needed in cup board to protect combustable use an approved ring. metal is not approved. 2.) maintain working clearence infront of subpanel. 3.) correctly identify ungrounded conductors at both ends. 4.) breaker to be sized per ampacity of conductors 336-26. 5.) new switches to be grounded 380-9. 6.) tighten water heater flex connectors. |