Permit: T03CM01327

Parcel: 10711175A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/19/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
04/30/2003 PLUMBING - INTERMEDIATE Partial Approval 1.) REVISED PLAN FOR PHASE TWO DWV ON SITE 3" ABS FROM DAY SPA TO PREP AREA OK
OK TO COVER THIS AREA ONLY AS HIGHLIGHTED ON PLAN.
04/29/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*REVIEWED WITH CONTRACTOR CORRECTIONS REQUIRED AND PLUMBING SECTION INTERPRETATION.
04/28/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*DOORS LOCKED NO ACCESS.
04/24/2003 PLUMBING - INTERMEDIATE Denied 1.) PLUMBING COVERED BEFORE APPROVAL AT KITCHEN SINK.
2.) SEE 804.1 94 UPC STANDPIPE RECEPTOR.
3.) SEE 706.2 UPC CHANGES IN DIRECTION NOTE #D.
4.) BATHTUB WASTE AND OVER FLOW REMOVED.
5.) CLEAN OFF CLOSET FLANGE FOR INSPECTION.
04/02/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) AS PER PLUMBING NOTES #4 & #5.
A.REQUIRED TWO PIPE DIAMETERS BETWEEN WEIR OF TRAP AND POINT OF VENT.
B.) STANDPIPE RECEPTOR MAY NOT EXCEED 30".
C.) FURNCO OF DBL SANTEE TO BE TWO PIPE SIZES LARGER THAN LARGEST INLET.
D.) BARREL OF DBL SANTEE TO BE TWO PIPES SIZES LARGER THAN LARGEST INLET.
E.) TUB OVERFLOW CUT IN HALF.
F.) WATER TEST ENTIRE ABS SYSTEM THROUGH ROOF.
G.) USE FHA STRAPS TO TIE-IN BASE PLATE.
H.) VENT WITHIN 12" OF PARAPET TO EXTEND TO ABOVE PARAPET.
I.) ISOLATE HOT FROM COLD WATER LINES TO AVOID HEAT TRANSFER.