Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 04/30/2003 | PLUMBING - INTERMEDIATE | Partial Approval | 1.) REVISED PLAN FOR PHASE TWO DWV ON SITE 3" ABS FROM DAY SPA TO PREP AREA OK OK TO COVER THIS AREA ONLY AS HIGHLIGHTED ON PLAN. |
|
| 04/29/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*REVIEWED WITH CONTRACTOR CORRECTIONS REQUIRED AND PLUMBING SECTION INTERPRETATION. | |
| 04/28/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*DOORS LOCKED NO ACCESS. | |
| 04/24/2003 | PLUMBING - INTERMEDIATE | Denied | 1.) PLUMBING COVERED BEFORE APPROVAL AT KITCHEN SINK. 2.) SEE 804.1 94 UPC STANDPIPE RECEPTOR. 3.) SEE 706.2 UPC CHANGES IN DIRECTION NOTE #D. 4.) BATHTUB WASTE AND OVER FLOW REMOVED. 5.) CLEAN OFF CLOSET FLANGE FOR INSPECTION. |
|
| 04/02/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) AS PER PLUMBING NOTES #4 & #5. A.REQUIRED TWO PIPE DIAMETERS BETWEEN WEIR OF TRAP AND POINT OF VENT. B.) STANDPIPE RECEPTOR MAY NOT EXCEED 30". C.) FURNCO OF DBL SANTEE TO BE TWO PIPE SIZES LARGER THAN LARGEST INLET. D.) BARREL OF DBL SANTEE TO BE TWO PIPES SIZES LARGER THAN LARGEST INLET. E.) TUB OVERFLOW CUT IN HALF. F.) WATER TEST ENTIRE ABS SYSTEM THROUGH ROOF. G.) USE FHA STRAPS TO TIE-IN BASE PLATE. H.) VENT WITHIN 12" OF PARAPET TO EXTEND TO ABOVE PARAPET. I.) ISOLATE HOT FROM COLD WATER LINES TO AVOID HEAT TRANSFER. |