Permit: T03CM01287

Parcel: 133160500

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/01/2003 MECHANICAL - FINAL Approved
04/29/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
CONDENSATE DRAINS LEAKING ONTO THE ROOF. SOME DRAIN PIPES DO NOT HAVE SLOPE. PROVIDE MIN 1/8" PER FT. BE SURE ALL EXPOSED PVC IS PAINTED.
04/25/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
1.) REMOVE PLASTIC DRAIN HOSE. USE COPPER.
2.) BLOCK & CLAMP PVC MAX. 4' SPACING. RECALL FOR INSPECTION.
04/11/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* TERMINATE CONDENSATE DRAINS TO AN APPROVED LOCATION. PROVIDE GREASE CUPS ON EXHAUST FANS . OK FOR TEMP C OF O.