Permit: T03CM01287

Parcel: 133160500

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/01/2003 ELECTRIC - INTERMEDIATE Approved
04/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK DOWN STAIR BATHROOM.
04/11/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
04/10/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* RECEIVED CK FOR $102 # 6016 FOR AFTER HOURS INSPECTON. 1) FIXTURE CANS TO HAVE SUPPORT WIRE AND RESET M/C CABLE IN FITTINGS AND SUPPORT M/C CABLE 2) REMOVE FLOATING KEYLESS FIXTURE 3) REMOVE CORDS PLUGGED IN ABOVE CEILING 4) ROMEX IS NOT AN APPROVED WIRING METHODE ABOVE CEILING LAYING ON TILES. 5) SUPPORT NEW VDU LABELING AS PER CODES 6) PROPERLY MOUNT BOX IN CEILING 7) AN APPROVED EXTENDER PLUGS ARE NEEDED.
04/09/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*BUILDING ELECTRIC WILL BE NEEDED TO BE MADE SAFE
1.) VERIFY LISTINGS FOR STAGE LIGHTING AND EQUIPMENT. ALSO INSTALL AS PER LABELING.
2.) FILL ALL UNUSED OPENING.
3.) M/C CABLE RAN IN PVC UNDERGROUND NOT ALLOWED.
OK M/C CABLE FOR EXIT LIGHTS
OK KITCHEN EQUIPMENT.
04/03/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
2.) FILL UNUSED OPENINGS IN BOXES.
3.) FINISH EXHAUST FAN FOR BATHROOM
4.) FINISH AT PANEL 'C' OK AREAS AS MARKED ON PLANS.
03/21/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*SERVICE TO BE MADE SAFE. RE TORQUE CONDUCTORS AND PROVIDE A LETTER. REPLACE MISSING PARTS & COVERS SET SERVICE UP FOR TEMP POWER TO OUTSIDE OF BUILDING. PLEASE ADD TEMP POWER FOR CONSTRUCTION TO PERMIT.