Permit: T03CM01281

Parcel: 125071680


Addresses:

2520 E 5TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM01281

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/24/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
12/23/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ PLEASE HAVE ELEC. CONTRACTOR SCHEDULE AN APPT.
07/31/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) INSTALLED PANEL AND TIME CLOCK DO NOT REFLECT PLANS AS DRAWN 2) WE NOW HAVE TAP CONDUCTORS LONGER THAN 25' FROM TIME CLOCK 240.21 3) PLEASE PROVIDE REJECTION PINS 4) POLE/BOLLARD TO HAVE ACCESS TO CONNECTIONS 5) CHECK GROUNDING NEXT TIME FOR POLES