Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/24/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 12/23/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ PLEASE HAVE ELEC. CONTRACTOR SCHEDULE AN APPT. |
| 07/31/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALLED PANEL AND TIME CLOCK DO NOT REFLECT PLANS AS DRAWN 2) WE NOW HAVE TAP CONDUCTORS LONGER THAN 25' FROM TIME CLOCK 240.21 3) PLEASE PROVIDE REJECTION PINS 4) POLE/BOLLARD TO HAVE ACCESS TO CONNECTIONS 5) CHECK GROUNDING NEXT TIME FOR POLES |