Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/17/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR C OF O. |
| 11/14/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) TRAPS ON CONDENSATE DRAIN LINES ARE FLATTENED AT BOTTOM OF TRAP. REPLACE TRAPS WITH FULL 3/4" I.D. TRAPS. PAINT EXPOSED PVC WITH LATEX PAINT. 2) PROVIDE A COUNTER FLASHING AT TOP OF A/C CURBS TO SEAL CURBS. 3) PROVIDE OUTSIDE AIR INTAKES AS PER PLAN. 4) PERMANENTLY LABEL UNITS ON ROOF WITH UNIT NUMBER AND SUITE NUMBER. 5) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM DISCONNECT TO A/C UNITS. RECALL FOR INSPECTION. |