Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR C OF O. |
| 11/17/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED BY DICK FURROW |
| 11/14/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1) BOXES MORE THAN 1/4" FROM SURFACE TO BOX IN NON CONBUSTABLES TO HAVE APPROVED EXTERIOR RING- 370-20 VMETAL NOT APPROVED. 2) COUIER PLATE NEED TO BE REMOVABLE TO ACCESS ELECTRIC. 3) GARBAGE DISPOSLE OUTLET TO BE ACCESSABLE. 4) FINISH FLOOR BOXES. 5) CIRCUIT DIRECTORY TO BE LEDGABLE. 6) FINISH WATER HEATER INSTALLATION. 7) MAINTAIN WIRING CLEARANCE IN FRONT OF A/C DISCONNECT. 8) ATTENA GROUND CONDUCTOR TO BE SIZED PER 810-21 |
| 07/09/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
BAD JUNCTION BOX- WE ALSO HAVE OVER FILL IN BOX |