Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/27/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 01/21/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*/ 1) M/C CABLE TO BE FOR EQUIPMENT PER 517.13 2) USE APPROVED M/C CONNECTOR NOT NM CABLE 3) BOND JUNCTION BOX PER 250.148 4) A REFEE HAS BEEN ACCESS PER ADMINISTRATIVE CODE |
| 01/16/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ LOCKED NO ACCESS. |
| 01/15/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED BY FURLOW |
| 01/14/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TO INSTALL NEW LIGHT |
| 01/07/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS TO MC PUMP 2) DENTAL LIGHTS HAVE BEEN FEILD MODIFIED-PLEASE PROVIDE A FEILD LISTING LABEL FOR MODIFICATION TO EQUIPMENT IN PATIENT CARE AREAS 3) PANEL LABELING TO BE PERMANENT |
| 12/19/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALL X-RAY EQUIPMENT 2) FINISH LIGHTING BOXES 3) PLEASE VERIFY CSA LISTING FOR DENTAL LIGHT WITH NO GROUND 4) GROUND FIXTURE 5) DISCONNECT TO HAVE WORKING CLEARANCES, BOND ENCLOSURER, USE CORRECT SIZE FUSE FOR CONDUCTOR AMPACITY 6) LABEL PANELS 7) FILL UNUSED OPENINGS IN FIXTURES |