Permit: T03CM01255

Parcel: 12418162D


Addresses:

931 S HIGHLAND AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/21/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/07/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) CONDUIT MUST BE SUPPORTED WITHIN 3' EACH TERMINATION AND AT 10' INTERVALS PER NEC USE BOX X FORMER TO BE BONDED PER 250 NEC ( SEPERATE DERIVED SYSTEMS) ALSO PER 250.104 3) PLUG UNUSED OPENING IN J-BOX EAST WALL 4) ROLL-UP DOOR DISCONNECTS AND CONTROLLERS IN VIOLATION OF DEDICATED ELECTRICAL SPACE SEE 110.26