Permit: T03CM01228

Parcel: 133341220

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/14/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/29/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) PROTECT CONDUCTORS IN BOXES 370.43 2) CANNOT HAVE CLASS 2 WIRING WITH CLASS 1 WIRING 3) AN APPROVED CONNECTOR IS NEEDED FOR EXHAUST FANS 4) TIGHTEN LOOSE TERMINATIONS AT SUB PANEL-ALSO ANTI OXIDE COMPOUND NEEDED FOR ALUMINIUM CONDUCTORS 5) BLDG INSPECTOR TO CHECK FIRE WALL PENETRATIONS 6) SUPPORT NM CABLE WITH IN 12" OF BOXES AND SE CABLE ON VERTICAL RISE 7) PROTECT CABLE PASSING THROUGH STUDS 8) PLEASE REMVOE NEUTRAL BOND SCREW 9) SE CABLE NOT SIZED PER PLAN AMPACITY