Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 10/29/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROTECT CONDUCTORS IN BOXES 370.43 2) CANNOT HAVE CLASS 2 WIRING WITH CLASS 1 WIRING 3) AN APPROVED CONNECTOR IS NEEDED FOR EXHAUST FANS 4) TIGHTEN LOOSE TERMINATIONS AT SUB PANEL-ALSO ANTI OXIDE COMPOUND NEEDED FOR ALUMINIUM CONDUCTORS 5) BLDG INSPECTOR TO CHECK FIRE WALL PENETRATIONS 6) SUPPORT NM CABLE WITH IN 12" OF BOXES AND SE CABLE ON VERTICAL RISE 7) PROTECT CABLE PASSING THROUGH STUDS 8) PLEASE REMVOE NEUTRAL BOND SCREW 9) SE CABLE NOT SIZED PER PLAN AMPACITY |