Inspection Status: Partial Approval
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/18/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000* APPROVAL SUBJECT TO ACCEPTANCE IF 1 LAYER BARRACADE WRAP, ALSO POST NEEDS PROPER CLEARANCE ABOVE FINISHED FLOOR. |
| 11/14/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 10/29/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED HOLD DOWN INFO IN LIEU OF THE MISSED HOLD DOWN STRAPS AND INSTALL. 2) PROPERLY INSTALL CLIPS (FILL IN AND NAIL AT TJI'S) NAILS MISSING. 3) BEARING WALLS NEED TO BE SHOT OR RED HEADED INTO CONCRETE AT BOTTOM PLATE. 4) BLOCK TRUSS AT RATED WALL TO MAINTAIN RATING W/ 5/8" DW. BOTH SIDES AND FIRE STOP ALL PENETRATIONS. 5) STRAP 2ND FLOOR TO 1ST FLOOR FRAMING. 6) FIRE BLOCK AS INDICATED. 7) LIFT POST OFF OF CONCRETE PORCH. |
| 09/12/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000* FIRE BARRIER MUST EXTEND THROUGH DORMER |