Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE A LOW COMBUSTION AIR OPENING IN WATER HEATER ENCLOSURE AND PROVIDE SCREEN IN OPENINGS 2) CONNECT GAS TO FURNACES 3) LEFT GAS CARD |
|
| 12/09/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) CONDENSATE DRAIN STILL HAS BACK PITCH. RECALL FOR INSPECTION 2) SHEET METAL CONNECTOR STILL MISSING FROM FLEX |