Permit: T03CM01227

Parcel: 133341220

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/11/2003 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*/ OK FOR SHEET ROCK.
12/03/2003 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PROVIDE MIN. 1/8" PER FT SLOPE ON HORIZONTAL SECTION OF CONDENSATE DRAIN BOTH UNITS. 2) PROVIDE BACKING AROUND CEILING BOX 1ST FLOOR. 3) PROVIDE WTR HTR VENT BOTH UNITS. 4) USE A SHEET METAL CONECTOR WHEN SPLICING FLEX DUCT. - ALL UNITS. 5) SUPPORT SHEET METAL DUCT IN CHASE BETTER.