Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/19/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE. OK FOR SHEET ROCK. |
| 12/18/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ CONDENSATE DRAIN LINES IN ATTIC DO NOT HAVE ADEQUATE SLOPE. UNIT 13101 WTR HTR VENT NOT CONNECTED TOGETHER CORRECTLY. LOCK THE JOINTS IN PLACE AFTER SNAPPING TOGETHER AND SECURE WITH STRAP. HANGER STRAP ON METAL DUCT IN CHASE NOT SECURED TO DUCT ON ONE SIDE. |