Permit: T03CM01217

Parcel: 133341220

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/11/2003 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*/ OK FOR SHEET ROCK.
12/09/2003 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) UNIT 3102 STILL MISSING BACK DRAFT DAMPER, ALUMINUM FLEX COMING APART AT END AND NOT TERMINATED THRU HOLE IN WALL. SECURE EXHAUST DUCTS SO THEY CAN'T FALL OUT OF OPENING 2) FLEX DUCT STILL MISSING SHEET METAL CONNECTOR 3) STILL MISSING BACKING AROUND CEILING BOX 4) RECALL FOR INSPECTION
12/03/2003 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) COMPLETE DRYER VENT TERMINATION AND BATH EXHAUST. 2) SUPPORT SHEET METAL DUCT TO 1ST FLOOR BETTER - ALL UNITS. 3) USE A SHHET METAL CONNECTOR WHEN SPLICING FLEX DUCT, ALL UNITS. 4) PROVIDE BACKING AROUND CEILING BOX 1ST FLOOR. 5) INSTALL WTR HTR VENT 3102. 6) 1ST FLOOR EXHAUST FAN MISSING BACKDRAFT DAMPER, UNIT 3102. RECALL FOR INSPECTION.