Permit: T03CM01211

Parcel: 106062890


Addresses:

1016 W THURBER ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM01211

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
06/10/2003 BUILDING - FINAL Denied 1)NEED LETTER FROM LICENSE ELECTRICIAN CONFIRMING ELECTRICAL IS TO CODE. 2) RELOCATE H20 GALV LINES W/ JOINT UNDER SLAB. 3) GAS CODE SHALL BE BEFORE UNION. 4) GAS TEST & PERMIT REQUIRED PRIOR TO RELEASING GAS.
04/30/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) UNDERGROUNDED 3 WIRE OUTLETS AT LAUNDRY 2) ROMEX (NON METALIC SHEATHED CABLE) EXPOSED AT LAUNDRY 3) ALL WIRING MUST TERMINATE IN APPROVED ELECTRIC BOXES 4) DRYER MUST BE ON A 4 WIRE (3 WIRE GROUNDED) CIRCUITS 5) COMBUSTIBLE MATERIAL WITHIN 6" OF SINGLE WALL FRANKLIN STOVE VENT PIPE 6) PROVIDE FRANLIN STOVE INSTALLATION INSTRUCTIONS 7) APPEARS TO BE NO FOUNDATION UNDER STRUCTURE. PROVIDE PROOF OF FOUNDATION AT ALL BEARING POINTS OF FAMILY ROOM AND PORCH 8) EXPOSE ALL FRAMING FOR FAMILY ROOM WALLS AND CEILING 9) UNSAFE ELECTRICAL DISONNECTS OVERSIZE FUSES FOR WIRING 10) GAS LINES REQUIRE SHUT OFF VALVES BEFORE UNIONS