Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*OK FOR C OF O. | |
| 04/21/2003 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 04/14/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*OPEN CEILING TO EXPOSE DUCT WORK FOR INSPECTION. STRAP ALL FLEX DUCT W/MIN 1 1/2" WIDE STRAP EVERY 5'. 2.) PROVIDE AN OUTSIDE AIR INTAKE 3.) PERMANENTLY LABEL A/C UNIT W/ ADDRESS. 4.) REPAIR ELEC. DISCONNECT. 5.) PROVIDE A SERVICE RECEPTACLE ON ROOF WITHIN 25' OF AC UNIT. 6.) PROVIDE A THERMOSTAT. 7.) RE ATTACH CANVAS SUN SHIELD |