Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM01175

Parcel: 13323110C


Addresses:

7525 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM01175

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) OK SOFFITS FOR ELECTRIC
10/30/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NO WORK PROGRESS-ALL AREAS COVERED WITHOUT INSPECTION APPROVAL 2) PLEASE PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE
10/23/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection 1) SUPPORT MC CABLE AS PER CODE 12" FROM CAN JUNCTION BOXES AND CIRCUIT JUNCTION BOXES. 2) WE HAVE EXPOSED CONDUCTORS AND UNUSED OPENINGS IN BOXES - ALSO SUPPORT AS PER CODE. 3) PLEASE REMOUNT SIGN GUTTER - NOT TO LAY ON BOARDS. 4) PLEASE PROVIDE A LADDER FOR ACCESS TO INSPECT GROUNDING AND MAKE-UP. 5) UNCOVER WIRING IN WALLS FOR INSPECTION. 6) WHERE ARE ON SITE PLANS?