Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) OK SOFFITS FOR ELECTRIC |
| 10/30/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) NO WORK PROGRESS-ALL AREAS COVERED WITHOUT INSPECTION APPROVAL 2) PLEASE PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE |
| 10/23/2003 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
1) SUPPORT MC CABLE AS PER CODE 12" FROM CAN JUNCTION BOXES AND CIRCUIT JUNCTION BOXES. 2) WE HAVE EXPOSED CONDUCTORS AND UNUSED OPENINGS IN BOXES - ALSO SUPPORT AS PER CODE. 3) PLEASE REMOUNT SIGN GUTTER - NOT TO LAY ON BOARDS. 4) PLEASE PROVIDE A LADDER FOR ACCESS TO INSPECT GROUNDING AND MAKE-UP. 5) UNCOVER WIRING IN WALLS FOR INSPECTION. 6) WHERE ARE ON SITE PLANS? |