Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2003 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) OK TO BACKFILL TRENCH. | |
| 08/07/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) BLDG SEWER FROM P.O.C. TO EXISTING BLDG SEWER TO C.O. IS OK. 2) OK TO BACKFILL TRENCH. | |
| 05/29/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*/ 1) PLEASE HAVE PLUMBING CONTRACTOR PRESENT A TIME OF NEXT INSPECTION 2) WATER CLOSET MUST BE PLUMBED IN A CONVENTIONAL MANNER 3) BLDG TWO WAY CLEANOUT IS REVERSED 4) MUST CONNECT TO BLDG SEWER NOT CLEANOUT AS REQUIRED | |
| 05/09/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*1.) ROUGH PLBG NOT TO PLAN OR CODE. 2.) MUST PROVIDE WATER TEST ON WASTE & VENT SYSTEM 10' HEAD. 3.) CAN NOT USE TWO WAY C.O. WITH A EXTENSION ON IT. THIS TWO WAY C.O. MSUT BE DIRECTIONAL FITTINGS. 4.) CAN NOT CONNECT 3" BLDG. SEWER TO C.O. EXTENSION CONNECT TO EXSISTING SEWER. 5.) MUST SHADE ALL HORIZONTAL WASTE LINE IN ITS ENTIRELY., |