Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM01143
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 06/05/2003 | FRAMING | Denied | IVRS - Inspection 0999* 1) NO TEST ON DWV'S & WATER LINES. 2) GUSSETT PLATE CUT AT FLOOR TRUSS. 3) NAIL PROTECT ELECTRICAL WITHIN 1 1/4 FROM EDGE OF STUD. 4) NAIL PROTECT PLUMBING WITHIN 1 1/2 FROM EDGE OF STUD. 5) REPLACE BOWED STUD NORTH WALL. 6) REPAIR OVER NOTCHED DBL TOP PLATE AT POWDER ROOM. 7) NAIL PROTECT VENT AT POWDER ROOM. 8) DBL TOP PLATE NORTH WALL POWDER ROOM OVER NOTCHED. 9) RE-FRAME NORTH EAST CORNER 2ND FLOOR. 10) INSULATE BEHIND MASTER TUB. 11) MISSING STRAPS FROM 1ST TO 2ND FLOOR AT STAIR. 12) FLOOR TRUSS AT NORTH EAST CORNER OVER NOTCHED. |