Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/19/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* CONDENSATE TERMINATION NOT INSTALLED CORRECTLY. CORRECT & RECALL FOR INSPECTION. |
|
| 03/13/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*IF YOU ARE GOING TO TERMINATE CONDENSATE INTO THE SEWER VENT YOU MUST USE A TEE ON THE VENT, NOT A HOLE DRILLED INTO THE SIDE OF THE VENT, AND TERMINATE INDIRECTLY WITH AIR GAP INTO THE 90 ELBOW POINTING UPWARD. THE VENT MUST BE MIN 2". THE 90 ELBOW MUST BE LARGER THAN THE DRAIN PIPE. 15 PSI TEST ON GAS LINE IS OK LEFT GAS CARD. RECALL FOR INSPECTION. |