Permit: T03CM01122

Parcel: 11203286B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/14/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
05/02/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) NO MORE THAN 360 IN A CONDUITS RUN.
2.) JUNCTION BOXES TO BE ACCESSABLE.
3.) PLEASE PROVIDE A LETTER AUTHURIZING USE OF M/C CABLE.
OK WALLS & HARD CEILING.
04/24/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO CLEAR SERVICE RELOCATE. OK CABLE DROP CALL
04/23/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection 1.) DISCONNECT REQUIRED PER PLAN #3 CONDUCTORS NOT #6. ALSO 1 1/4 CONDUIT. PANEL "B"
2.) PLANS CALLS FOR 3/0 CU.FOR FEEDERS TO PANEL "A" NOT ALUM.
3.) STRAP WATER BOND WIRE.
4.) COMPLETE UFER AND METER BOND, MAIN BONDING JUMPER TERMINATION.
5.) SUPPORT RISER.
2 HRS PAID CK 17458 102.00 3HRS STANDBY 153.00 PAID IN CASH.
03/21/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK 1/0 TO REBAR.