Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 05/02/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) NO MORE THAN 360 IN A CONDUITS RUN. 2.) JUNCTION BOXES TO BE ACCESSABLE. 3.) PLEASE PROVIDE A LETTER AUTHURIZING USE OF M/C CABLE. OK WALLS & HARD CEILING. |
|
| 04/24/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR SERVICE RELOCATE. OK CABLE DROP CALL | |
| 04/23/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | 1.) DISCONNECT REQUIRED PER PLAN #3 CONDUCTORS NOT #6. ALSO 1 1/4 CONDUIT. PANEL "B" 2.) PLANS CALLS FOR 3/0 CU.FOR FEEDERS TO PANEL "A" NOT ALUM. 3.) STRAP WATER BOND WIRE. 4.) COMPLETE UFER AND METER BOND, MAIN BONDING JUMPER TERMINATION. 5.) SUPPORT RISER. 2 HRS PAID CK 17458 102.00 3HRS STANDBY 153.00 PAID IN CASH. |
|
| 03/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 1/0 TO REBAR. |