Permit: T03CM01114

Parcel: 107010300

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM01114

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*ABS TRAP ARM OK
2.) IM CONCERNED THAT STRUCTURAL INTEGRITY ON A BEARING WALL HAS BEEN COMPROMISED, HOWEVER WILL DEFER TO BLDG INSPECTOR.
03/26/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) A SANTEE MAY NOT LAY ON ITS BACK.
2.) A 90 CLEAN OUT EXTENSION SHALL BE MADE THROUGH A WYE BRANCH FITTINGS OR EQUIVLENT SWEEP.
3.) THSI TIME YOU WILL PAY A REINSPECTION FEE.
03/25/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) PLEASE READ NOTE FROM 3/24/03 AND COMPLY.
2.) CONTRACTOR TO PAY RE-INSPECTION FEE.
03/24/2003 PLUMBING - INTERMEDIATE Denied 1.) A CLEAN OUT MAY NOT CONNECT HORIZONTALLY TO A HORIZONTAL DRAIN LINE.
03/23/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*PLEASE COMPLY WITH THE NOTES LEFT ON 3/20/03 DO NOT RECALL UNTIL CORRECTIONS HAVE BEEN MADE.
03/20/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) A TRAP ARM MAY ONLY CHANGE DIRECTION 90 WITHOUT AN ADDITIONAL CLEAN OUT
2.) BOTH SIDES OF NOT STUD MUST BE TIED BACK IN WITH FHA STRAP.