Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/14/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 05/07/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) CLIPS UNDER STAIRS MISSING NAILS AND HANGER MISSING 2) MECHANICAL NOT BLOCKED AT TOP OF STAIRS (RETURN) 3) NAIL PROTECT DRYER VENT UPSTAIRS 4) OUTLET MISSING SOUTH WALL UPSTAIRS BEDROOM 5) NAIL PROTECT PLUMBING UPSTAIRS BATH WITHIN 1 1/2 FROM EDGE OF STUD 6) NAIL PROTECT ELECTRIC IN MASTER BATH 7) NAIL PROTECT ELECTRIC BOTH SIDES OF WINDOW AT SOUTH WEST WALL 8) DOUBLE TOP PLATE AT LIVING ROOM NOT STAGGERED PER CODE COVERED BY CLIPS-REPLACE 9) STOPPED INSPECTION 10) NEXT FAILURE WILL RESULT IN RE-FEES |
| 05/01/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) DWV'S FAILED TEST 2) BEARING STUD IN GARAGE OVER NOTCHED 3) DOUBLE TOP PLATE IN GARAGE REQUIRES ENGINEERING REPAIR 4) DOUBLE TOP PLATE AT GARAGE WEST WALL REQUIRES 16G STRAPS W/ 6 16D NAILS ON EACH SIDE 5) STOPPED INSPECTION |