Permit: T03CM01098

Parcel: 129042980


Addresses:

1934 E 14TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/17/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
1.) PRESSURE TEST OK
PIPING OK
VALVES AND FLEXES OK
2.) OK FOR GAS
3.) UCC LEFT AT METER
SW GAS 889-1888.
03/06/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*PROVIDE AGA APPROVED VALVES AT REACH FIXTURE
2.) HAND PIPE THROU WALL OF FURNACE.
3.) PROVIDE A PRESSURE TEST ON COMPLETE SYSTEM OF NOT LESS THEN 10LBS.
4.) WILL REQUIRE AN APPEAL FOR RELIEF LINE TO PAN & 125LBS RELIEF AT SERVICE.
5.) PROVIDE RELIEF VALVE AT WATER HEATER.