Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM01098
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* 1.) PRESSURE TEST OK PIPING OK VALVES AND FLEXES OK 2.) OK FOR GAS 3.) UCC LEFT AT METER SW GAS 889-1888. |
|
03/06/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*PROVIDE AGA APPROVED VALVES AT REACH FIXTURE 2.) HAND PIPE THROU WALL OF FURNACE. 3.) PROVIDE A PRESSURE TEST ON COMPLETE SYSTEM OF NOT LESS THEN 10LBS. 4.) WILL REQUIRE AN APPEAL FOR RELIEF LINE TO PAN & 125LBS RELIEF AT SERVICE. 5.) PROVIDE RELIEF VALVE AT WATER HEATER. |