Date Description Inspector Results Comments
12/05/2003 ELECTRIC - PROGRESS Approved IVRS - Inspection 0000*
11/20/2003 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection 0000*/ 1) BOND ALL SERVICES PER 250.58 2) IDENTIFY HIGH LEG CONDUCTORS AS PER CODE 3) BONDING JUMPERS PER 250.102 AND TABLE250.66 4) MAKE SURE PLANS ARE REFLECTIVE OF SERVICE BEING INSTALLED