Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2003 |
ELECTRIC - PROGRESS |
|
Approved |
IVRS - Inspection 0000* |
| 11/20/2003 |
ELECTRIC - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) BOND ALL SERVICES PER 250.58 2) IDENTIFY HIGH LEG CONDUCTORS AS PER CODE 3) BONDING JUMPERS PER 250.102 AND TABLE250.66 4) MAKE SURE PLANS ARE REFLECTIVE OF SERVICE BEING INSTALLED |