Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T03CM01093
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2003 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection 0000* | |
| 11/20/2003 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection 0000*/ 1) BOND ALL SERVICES PER 250.58 2) IDENTIFY HIGH LEG CONDUCTORS AS PER CODE 3) BONDING JUMPERS PER 250.102 AND TABLE250.66 4) MAKE SURE PLANS ARE REFLECTIVE OF SERVICE BEING INSTALLED |